Setra SRCM room condition monitor
A room condition monitor built around an industry-best accuracy, dead-ended differential pressure sensor, with temperature, humidity and one user-defined value on a 4.3-inch colour touch screen.

Setra SRCM is a room condition monitor made by Setra Systems for isolation and protective environment rooms. It measures low differential pressure with ±0.25% or ±0.5% FS accuracy and monitors 4 parameters: pressure, temperature, humidity and one user-defined value such as air changes per hour. Electrex Arabia supplies, installs and commissions Setra SRCM in Saudi Arabia.
Technical specifications
| Monitored values | Differential pressure, temperature, humidity, 1 user-defined (e.g. ACH or CO₂) |
| Rooms | 1 room typical, up to 2 rooms per unit |
| Sensor | On-board dead-ended low differential pressure sensor |
| Pressure ranges | ±12.5 to ±1000 Pa (±0.05 to ±5.0 in WC) |
| Accuracy | ±0.25% FS (code F) or ±0.5% FS (code H) |
| Display | 4.3" TFT colour touch screen, 480 × 272, dimmable, custom room names |
| Alarms | Configurable audible and visual alarms, door alarm digital input |
| Outputs | 4-20 mA, 0-5 / 0-10 VDC, SPDT alarm relay, BACnet option (A2) |
| Power | 18-32 VAC, 10 W max |
| Enclosure | IP54 wipe-down flush face, UL94 V-0 |
| Mounting | Triple-gang double-deep electrical box |
| Calibration | Push-button zero and span; USB configuration cloning |
Specifications from the Setra Systems data sheet; final selection follows the approved project submittal.
Applications
- Airborne infection isolation rooms
- Protective environment rooms
- Isolation suites with ante-rooms
- Laboratories
- Pharmacy clean rooms
What we deliver
- Design and engineering of the monitoring scheme
- Supply of room monitors and sensors
- Installation and cabling
- Programming and configuration
- BACnet integration with the BMS
- Testing, commissioning and handover
- After-sales support
FAQ
What does Setra SRCM monitor?
Setra SRCM monitors 4 parameters: differential pressure from its on-board sensor, temperature, humidity and one user-defined value such as air changes per hour or CO₂.
Why is the SRCM sensor dead-ended?
A dead-ended sensor does not let air flow through it, so contaminated air from an isolation room cannot pass through the monitor.
Setra SRCM or Setra FLEX?
Choose SRCM for isolation and protective rooms where pressure accuracy is the priority and 4 parameters are enough. Choose FLEX when you need 6 parameters per room, a 7-inch screen or room control.
Where can I buy Setra SRCM in Saudi Arabia?
Electrex Arabia supplies, installs and commissions Setra SRCM monitors across Saudi Arabia, including BMS integration.
Setra, Setra Systems, FLEX, SRCM and Setra Lite are trademarks of Setra Systems, Inc. Product names are used only to identify the equipment we supply and install. Specifications are from Setra's published data sheets and may change; the final selection follows the approved project submittal.
Have drawings or a BOQ? Send them over.
Our engineers reply with a technical and commercial offer.